PCE-ET 5000
Earth Tester
The grounding meter is a versatile ohmmeter.
With this grounding meter a variety of resistance measurements can be performed. Thus, with the grounding meter, the possibility exists to perform a normal resistance measurement of 2- or 4-pole application. It is also possible to determine the resistance of the soil with the grounding meter. For the measurement of earth resistance corresponding earth spikes are included in the scope of supply. These ground spikes can easily be connected to the grounding device via the supplied separate 20 meter / 66 ft cable.
Mobile use thanks to battery and batteries
Data memory for later analysis on the PC
Visual connection aid for easy operation
Alarm in case of incorrect connection of the measuring line
Direct and indirect resistance measurement
Interference currents, interference voltages, frequencies
SPECIFICATION
​
Data storage 100 readings
Operating conditions 0 ... 40°C / 32 ... 104°F, < 80% RH (non-condensing)
Charge ambient conditions to the battery 10 ... 40°C / 50 ... 104°F, < 80% rh (non-condensing)
Storage conditions -10 ... 50°C / 50 ... 122°F, < 90% rh (non-condensing)
Storage conditions for the battery -20 ... 30°C / -4 ... 86°F, < 80% rh (non-condensing)
Storage height < 12,000 m / 39,370 ft
Operating altitude < 2,000 m / 6,561 ft
Clamp diameter 51 mm
Display Backlit LCD, 9,999 digits
Display measuring range exceeded > LIMIT
Display below measuring range -
Measuring frequency earthing resistance / leakage current 1 Hz (If the average value function is activated: one value every four seconds)
Measuring frequency voltage measurement 2 Hz
Measuring frequency interference voltage 4 Hz
Measuring frequency interference frequency 1 Hz
Measuring frequency interference current 1 Hz
interfaces Measuring connection: E, ES, S, H, pliers
connection USB-B, charging connection
Power supply batteries 6 x 1.5V D LR14 batteries
Power supply battery 1 x 7.2V nickel-metal hydride battery pack
Power supply power supply Primary: 100 ... 240V, 50 ... 60 Hz
Secondary: 12V, 3A
Max. Power consumption with power supply 15V A
Max. Power consumption with battery or rechargeable battery 6V A
Running time in battery mode About 5 hours
Running time in the battery About 9 hours (without backlight)
Maximum input voltage
Maximum input voltage relative to earth 300V rms (CAT III)
Insulation thickness 6880V AC: 15 seconds
Overvoltage protection 250V AC between the connections
Dimensions 260 x 125 x 280 mm / 10.2 x 4.9 x 11 in
Weight About 2.5 kg / 5.5 lbs
Standardize Safety: EN61010-1: 2001, EN61010-031: 2002
Pollution degree 2, CAT III 300V,
EMC: EN61000-3-2: 2000, IEC61326-1: 1997 A